Three-Phase Power Quality And Energy Analyzer w/o Clamps

Fluke 435 Series II Power Quality and Energy Analyser

Advanced power quality functions, unprecedented energy analysis capabilities


Think of the Fluke 435 II Power Quality and Energy Analyzer as your insurance policy. No matter what goes wrong in your facility, with the 435 II you will always be prepared. Equipped with advanced power quality functions and energy monetization capabilities, there is no electrical issue this model can’t handle.


Fluke 435 Comes Supplied With:

  • BC430 Power Adapter
  • International plug adapter set
  • BP290 (Single capacity Li-ion battery 28 Wh (8 hours or more)
  • TLS430 Test lead and Alligator clip set
  • WC100 color coding clips and regional decals
  • i430flex-TF, 24 inch (61 cm) length, 4 flexible current probes
  • 8 GB SD card
  • PowerLog on CD (includes operator manuals in PDF format)
  • USB cable A - Mini B

*Fluke 435/BASIC comes supplied as above without the i430flex clamps

 

Typical Applications:

  • PowerWave data capture – capture fast RMS values to see every waveform so you can determine how the voltage, current and frequency values are interacting
  • Power inverter efficiency – Power inverter efficiency
  • Energy monetization – calculate the fiscal cost of energy waste due to poor power quality
  • Energy assessment – quantify the before and after installation improvements in energy consumption to justify energy saving devices
  • Frontline troubleshooting – quickly diagnose problems on-screen to get your operation back online
  • Predictive maintenance – detect and prevent power quality issues before they cause downtime
  • Long-term analysis – uncover hard-to-find or intermittent issues
  • Load studies – verify electrical system capacity before adding loads


PowerWave data capture 


For some users, loads switching is a cause of power quality problems. When loads switch on, the current draw sometimes causes the voltage to drop to a level that causes other equipment to malfunction. The PowerWave function available in the 435 and 437 Series II models enables users to capture voltage, current and frequency signals simultaneously at a high speed to see which interaction is potentially causing problems. PowerWave goes beyond standard power quality measurements; PowerWave’s fast data capture mode enables system dynamics to be characterized.

Waveforms for voltage and current are continuously captured for the specified time, and are displayed on screen in high detail; the power waveform is derived from the data. In addition, half-cycle RMS values for voltage, current, power and frequency can be stored and retrieved for analysis. This feature is particularly useful for testing of standby generation systems and UPS systems where reliable switch-on can be vital.

  • Power inverter efficiency: Simultaneously measure AC output power and DC input power for power electronics systems using optional DC clamp.
  • PowerWave data capture: Capture fast RMS data, show half-cycle and waveforms to characterize electrical system dynamics (generator start-ups, UPS switching etc.).
  • Energy loss calculator: Classic active and reactive power measurements, unbalance and harmonic power, are quantified to pinpoint the fiscal costs of energy losses.
  • Troubleshoot real-time: Analyze the trends using the cursors and zoom tools.
  • Highest safety rating in the industry: 600 V CAT IV/1000 V CAT III rated for use at the service entrance.
  • Measure all three phases and neutral: With included four flexible current probes with enhanced thin flex design to fit into the tightest places.
  • Automatic Trending: Every measurement is always automatically recorded, without any set-up.
  • System-Monitor: Ten power quality parameters on one screen according to EN50160 power quality standard.
  • Logger function: Configure for any test condition with memory for up to 600 parameters at user defined intervals.
  • View graphs and generate reports: With included analysis software.
  • Battery life: Seven hours operating time per charge on Li-ion battery pack.
 

Power inverter efficiency 


Power inverters take DC current and transform it into AC current, or vice versa. Solar generation systems usually include an inverter that takes the DC energy from the solar cells and converts it to useful AC power. Inverters can lose performance over time and need to be checked. By comparing the input power with the output power you can determine the system efficiency. The 430 series II can measure the efficiency of such inverters by simultaneously measuring the DC and AC power of a system to determine how much power is lost in the conversion process.

         
Logging function allows you to customize measurement selections and provides instantaneous analysis of user-selectable parameters.Measure and record power
(W), VA and VARs, PF and energy consumption.
Track harmonics up to the 50th, and measure and
record THD in accordance with IEC61000-4-7 requirements


Product specifications
 ModelMeasurement rangeResolutionAccuracy
Volt
Vrms (ac+dc)435-II1 V to 1000 V phase to neutral0.01 V± 0.1% of nominal voltage**** 
Vpk 1 Vpk to 1400 Vpk1 V5% of nominal voltage
Voltage Crest Factor (CF) 1.0 > 2.80.01± 5 %
Vrms½435-II 0.1 V± 0.2% of nominal voltage
Vfund435-II 0.1 V± 0.1% of nominal voltage
Amps (accuracy excluding clamp accuracy)
Amps (ac +dc)i430-Flex 1x 5 A to 6000 A1 A± 0.5% ± 5 counts
i430-Flex 10x0.5 A to 600 A0.1 A± 0.5% ± 5 counts
1mV/A 1x5 A to 2000 A1A± 0.5% ± 5 counts
1mV/A 10x0.5 A A to 200 A (ac only)0.1 A± 0.5% ± 5 counts
Apki430-Flex 8400 Apk 1 Arms± 5 %
1mV/A5500 Apk1 Arms± 5 %
A Crest Factor (CF) 1 to 100.01± 5 %
Amps½i430-Flex 1x 5 A to 6000 A 1 A ± 1% ± 10 counts 
i430-Flex 10x0.5 A to 600 A0.1 A ± 1% ± 10 counts
1mV/A 1x  5 A to 2000 A 1A ± 1% ± 10 counts
1mV/A 10x0.5 A A to 200 A (ac only)0.1 A± 1% ± 10 counts
Afundi430-Flex 1x 5 A to 6000 A1 A± 0.5% ± 5 counts 
i430-Flex 10x 0.5 A to 600 A0.1 A± 0.5% ± 5 counts
1mV/A 1x 5 A to 2000 A1A± 0.5% ± 5 counts
1mV/A 10x 0.5 A A to 200 A (ac only)0.1 A± 0.5% ± 5 counts
Hz
HzFluke 435 @ 50 Hz nominal 42.500 Hz to 57.500 Hz
0.001 Hz

± 0.01 Hz
Fluke 435 @ 60 Hz nominal 51.000 Hz to 69.000 Hz
0.001 Hz

± 0.01 Hz
Power
Watts (VA, var)i430-Flex max 6000 MW0.1 W to 1 MW± 1% ± 10 counts
1 mV/Amax 2000 MW0.1 W to 1 MW± 1% ± 10 counts
Power factor (Cos j/DPF) 0 to 10.001± 0.1% @ nominal load conditions
Energy
kWh (kVAh, kvarh)i430-Flex 10xDepends on clamp scaling and V nominal± 1% ± 10 counts
Energy lossi430-Flex 10xDepends on clamp scaling and V nominal± 1% ± 10 counts Excluding line resistance accuracy
Harmonics
Harmonic order (n) DC, 1 to 50 Grouping: Harmonic groups according to IEC 61000-4-7
Inter-harmonic order (n) OFF, 1 to 50 Grouping: Harmonic and Interharmonic subgroups according to IEC 61000-4-7
Volts%f0.0 % to 100 %0.1 %± 0.1% ± n x 0.1 %
%r0.0 % to 100 %0.1 %± 0.1% ± n x 0.4 %
Absolute0.0 to 1000 V0.1 V± 5% *
THD0.0 % to 100 %0.1 %± 2.5 %
Amps%f0.0 % to 100 %0.1 %± 0.1% ± n x 0.1%
%r0.0 % to 100 %0.1 %± 0.1% ± n x 0.4 %
Absolute0.0 to 600 A0.1 A± 5% ± 5 counts
THD0.0 % to 100 %0.1 %± 2.5 %
Watts%f or %r 0.0 % to 100 %0.1 %± n x 2%
AbsoluteDepends on clamp scaling and V nominal ± 5% ± n x 2 % ± 10 counts
THD0.0 % to 100 %  0.1 %± 5 %
Phase Angle -360° to +0°± n x 1°
Flicker
Plt, Pst, Pst(1min) Pinst 0.00 to 20.000.01± 5 %
Unbalance
Volts%0.0 % to 20.0 %0.1 %± 0.1 %
Amps%0.0 % to 20.0 %0.1%± 1 %
Mains signaling
Threshold levels Threshold, limits and signaling duration is programable for two signaling frequencies
Signaling frequency 60 Hz to 3000 Hz0.1 Hz 
Relative V% 0 % to 100 %0.10 %± 0.4 %
Absolute V3s (3 second avg.) 0.0 V to 1000 V0.1 V± 5 % of nominal voltage

 


General specifications

CaseDesign Rugged, shock proof with integrated protective holster Drip and dust proof IP51 according to IEC60529 when used in tilt stand position Shock and vibration Shock 30 g, vibration: 3 g sinusoid, random 0.03 g 2 /Hz according to MIL-PRF-28800F Class 2
DisplayBrightness: 200 cd/m 2 typ. using power adapter, 90 cd/m 2 typical using battery power Size: 127 mm x 88 mm (153 mm/6.0 in diagonal) LCD Resolution: 320 x 240 pixels Contrast and brightness: user-adjustable, temperature compensated
Memory8GB SD card (SDHC compliant, FAT32 formatted) standard, upto 32GB optionally Screen save and multiple data memories for storing data including recordings (dependent on memory size)
Real-time clockTime and date stamp for Trend mode, Transient display, System Monitor and event capture

Environmenta


Operating temperature0 °C ~ +40 °C; +40 °C ~ +50 °C excl. battery
Storage temperature-20 °C ~ +60 °C
Humidity+10 °C ~ +30 °C: 95% RH non-condensing 
+30 °C ~ +40 °C: 75% RH non-condensing 
+40 °C ~ +50 °C: 45% RH non-condensing
Maximum operating altitudeUp to 2,000 m (6666 ft) for CAT IV 600 V, CAT III 1000 V 
Up to 3,000 m (10,000 ft) for CAT III 600 V, CAT II 1000 V 
Maximum storage altitude 12 km (40,000 ft)
Electro-Magnetic-Compatibility (EMC)EN 61326 (2005-12) for emission and immunity
Interfacesmini-USB-B, Isolated USB port for PC connectivity SD card slot accessible behind instrument battery
WarrantyThree years (parts and labor) on main instrument, one year on accessories




    * ± 5 % if ≥ 1 % of nominal voltage ± 0.05 % of nominal voltage if < 1% of nominal voltage 
   ** 50Hz/60Hz nominal frequency according to IEC 61000-4-30
 *** 400Hz measurements are not supported for Flicker, Mains Signaling and Monitor Mode. 
****for nominal voltage 50 V to 500 V

 


 

Welcome to Local City

Asked Question

Lorem ipsum dolor sit amet, consectetur adipiscing elit. Praesent in accumsan dui. Donec imperdiet, nisl non pharetra convallis, nunc sapien laoreet massa, ac elementum arcu neque vitae enim. Praesent convallis leo est, scelerisque tincidunt magna ultricies eu. Ut placerat est a eros faucibus feugiat. Nullam a urna sit amet sem porttitor malesuada a quis nibh. In hac habitasse platea dictumst. Donec sit amet auctor leo. Sed venenatis posuere risus quis dictum. Vivamus ullamcorper orci vitae eros tincidunt, a aliquet lacus dapibus. Sed consectetur, est vel tincidunt imperdiet, justo est dignissim lorem, nec tincidunt lacus lacus ac risus. Cras pretium enim nec vestibulum aliquam. Vestibulum ante ipsum primis in faucibus orci luctus et ultrices posuere cubilia Curae;
Lorem ipsum dolor sit amet, consectetur adipiscing elit. Praesent in accumsan dui. Donec imperdiet, nisl non pharetra convallis, nunc sapien laoreet massa, ac elementum arcu neque vitae enim. Praesent convallis leo est, scelerisque tincidunt magna ultricies eu. Ut placerat est a eros faucibus feugiat. Nullam a urna sit amet sem porttitor malesuada a quis nibh. In hac habitasse platea dictumst. Donec sit amet auctor leo. Sed venenatis posuere risus quis dictum. Vivamus ullamcorper orci vitae eros tincidunt, a aliquet lacus dapibus. Sed consectetur, est vel tincidunt imperdiet, justo est dignissim lorem, nec tincidunt lacus lacus ac risus. Cras pretium enim nec vestibulum aliquam. Vestibulum ante ipsum primis in faucibus orci luctus et ultrices posuere cubilia Curae;
Lorem ipsum dolor sit amet, consectetur adipiscing elit. Praesent in accumsan dui. Donec imperdiet, nisl non pharetra convallis, nunc sapien laoreet massa, ac elementum arcu neque vitae enim. Praesent convallis leo est, scelerisque tincidunt magna ultricies eu. Ut placerat est a eros faucibus feugiat. Nullam a urna sit amet sem porttitor malesuada a quis nibh. In hac habitasse platea dictumst. Donec sit amet auctor leo. Sed venenatis posuere risus quis dictum. Vivamus ullamcorper orci vitae eros tincidunt, a aliquet lacus dapibus. Sed consectetur, est vel tincidunt imperdiet, justo est dignissim lorem, nec tincidunt lacus lacus ac risus. Cras pretium enim nec vestibulum aliquam. Vestibulum ante ipsum primis in faucibus orci luctus et ultrices posuere cubilia Curae
Lorem ipsum dolor sit amet, consectetur adipiscing elit. Praesent in accumsan dui. Donec imperdiet, nisl non pharetra convallis, nunc sapien laoreet massa, ac elementum arcu neque vitae enim. Praesent convallis leo est, scelerisque tincidunt magna ultricies eu. Ut placerat est a eros faucibus feugiat. Nullam a urna sit amet sem porttitor malesuada a quis nibh. In hac habitasse platea dictumst. Donec sit amet auctor leo. Sed venenatis posuere risus quis dictum. Vivamus ullamcorper orci vitae eros tincidunt, a aliquet lacus dapibus. Sed consectetur, est vel tincidunt imperdiet, justo est dignissim lorem, nec tincidunt lacus lacus ac risus. Cras pretium enim nec vestibulum aliquam. Vestibulum ante ipsum primis in faucibus orci luctus et ultrices posuere cubilia Curae;