Bartec Measuring transducer Pt100 galvanically isolated for zone 1/21
-
NG # 003915-HW-WIN-O15
Manufactured by:
The MODEX series includes a temperature measuring transducer mounted on-site in the same way as a rail-mounted terminal.
Specification
Protection class Module: IP 66/IEC 60529
Terminals: IP 20/IEC 60529Material High-quality thermoplastic Installation TH 35 x 15 (7.5) EN/IEC 60715 Storage temperature -40 °C to +60 °C Weight 0.250 kg Temperature range -50 °C to +400 °C (see data sheet) Voltage DC 24 V -10 %/+20 % Output current Load independent current: 4 to 20 mA Power Power consumption: 1.6 W Connection Terminals 2.5 mm², fine stranded
Description
The module transforms the signal received from the Pt100 temperature sensor into a proportional, load independent 4 to 20 mA output signal. The sensor circuit is intrinsically safe according to Ex protection type Ex ia. An output current exceeding the 4 to 20 mA range signals a senor fault (open/short circuit). The Pt100 temperature sensor can be operated in 2-wire or 3-wire circuits in Zone 0 or Zone 1.