EchoBeam® LR83 80-GHz Radar Liquid and Solids Level Sensor Transmitter

EchoBeam® LR83 80-GHz Radar Liquid and Solids Level Sensor Transmitter

Flowline
TF: 08203-HW-Flow-0203
Overview

The EchoBeam® LR83 is a reliable and easy-to-use non-contact level sensor transmitter utilizing advanced 80-GHz radar technology. Unaffected by most media, process, or environmental conditions, it delivers accurate, continuous level measurement for demanding industrial applications. Configuration is simple using the LevelTap™ App, LCD display, HART, or Modbus communication.


 

SPECIFICATIONS

Maximum range: Liquid: 98.4’ (30m) with media dielectric ≥ 10 and no agitation; Solids: 49.2’ (15m) with media dielectric ≥ 6 and no dust

Frequency: 80-GHz., W-band, FMCW

Accuracy: 0.4m to 30m: ± 2mm; 0.00m to 0.39m: ± 10mm

Dead band: 0” (0mm)

Beam angle: 6°

Min. dielectric: ≥ 1.6

Bluetooth version: Bluetooth 5.0

Bluetooth range: 26.2′ (8m)

Configuration: LevelTapTM App (IOS & Android) or push button

Memory: Non-volatile

Display type: LCD, dot matrix

Signal output: _ _ _ 0: 4-20 mA, two-wire, HART 7; 0 _ _ 1: Modbus, RS485, 9600 baud

Max. signal dist.: _ _ _ 0: 1,000’ (304m); 0 _ _ 1: 3,937’ (1200m)

Signal fail-safe: Selectable high, low or hold last value

Wire interface: _ _ _ 0: 2-pole terminal block; 0 _ _ 1: 4-pole terminal block

Supply voltage: _ _ _ 0: 12-30 VDC; 0 _ _ 1: 9-27 VDC

Max. consumption: _ _ _ 0: 22.5 mA; 0 _ _ 1: 1.5 watt

Process temp.: F: -40° to 212°, C: -40° to 100°

Temp. comp.: Automatic

Storage temp.: F: -40° to 176°, C: -40° to 80°

Pressure: -14.5 to 43.5 psi (-1 to 3 bar)

Enclosure rating: NEMA 4X (IP66/67)

Conduit connect.: _ _ 0 _: 1/2” NPT; _ _ 1 _: M20

Encl. material: PBT-FR (polybutylene terephthalate)

Encl. cap material: PC (clear polycarbonate)

Antenna material: PVDF (natural polyvinylidene fluoride)

Process mount: _ _ 0 _: 1 1/2” NPT; _ _ 1 _: 1 1/2” G

Mount gasket: _ _ 0 _: N/a; _ _ 1 _: Viton GLT (fluoroelastomer)

Classification: 0 _ _ _: General purpose, cCSAus; 1 _ _ 0: Intrinsically safe, cCSAus, ATEX, IECEx

Approvals: 0 _ _ _: C22.2 No. 61010-1-12; 1 _ _ 0: Ex ia IIC T6…T4 Ga Ex ia IIIC T85…T135 Da Class I, Zone0, AEx ia IIC T6…T4 Ga Zone 20,AEx ia IIIC T85…T135 Da Class I, Division 1, Groups A,B,C,D T6…T4 Class II, Division1, Groups E,F,G T6…T4

Entity parameters: 0 _ _ _: N/a; 1 _ _ 0: Install per control drawing #610135

The LR83 is available in general-purpose or intrinsically safe models and provides continuous level measurement up to 98.4 ft (30 m) for liquids and 49.2 ft (15 m) for solids. It outputs a 4–20 mA signal with HART or Modbus protocol. Wireless Bluetooth configuration via the LevelTap™ App allows users to monitor level, verify status, and adjust settings safely from ground level or nearby access points.