89/2, West Panthapath,Dhaka
Measurement Range | 0.1 μΩ to 999.9 mΩ (Subject to supply voltage and leads used) |
Accuracy | Voltage ±0.5% ± 0.1 mV Current ±0.5% ± 0.1 A Resistance: Better than 1% from 300 μΩ to 100 mΩ Better than ±2% from 100 μΩ to 300 μΩ |
Current Lead Resistance (Megger Leads) | 2 x 5 m 25 mm2 current leads 8 m 2 x 5 m 50 mm2 current leads 4 mΩ 2 x 10 m 70 mm2 current leads 5.4 mΩ 2 x 15 m 95 mm2 current leads 6 mΩ |
Maximum Continuous Test Time | More than 10 minutes at 200 A @ 20 ºC ambient. |
Power Supply for DLRO200 for full output (unsmoothed DC) | 100 to 265 V 50/60 Hz with a load less than 19 mΩ (supply >207 V rms), or 11 mΩ (115 V rms) including current leads |
Power Supply for DLRO200-115V for full output (additional smoothing) | 100 to 130 V 50/60 Hz with a load less than 11 mΩ including current leads |
Test Modes | Manual, Auto, Continuous. |
Test Time | 10 seconds NORMAL /AUTO mode. Refreshed every 2 seconds in CONTINUOUS mode |
Display | Large, high resolution backlit liquid crystal display |
Warnings | Current flowing: - LED. Other warnings are shown on the lcd display |
Data Transfer | Real time or batch download via RS232 using Download Manager. |
Storage Capacity | 300 result sets and memo, battery backed for 10 years. |
Memo Field | 160 characters max. |
Test Current Range | 10 A to 200 A d.c. |
Accuracy | ±2% ±2 A |
Voltmeter Input Impedance | >200 kΩ |
Hum Rejection | 5 V rms 50 Hz/60 Hz |
Temperature Operation | -10 to +50 ºC (-14 to +122 ºF) |
Storage | -25 to +65 ºC (-13 to 149 ºF) |
Calibration | 20 ºC |
Co-Efficient | <0.05% per ºC |
Max Humidity | 95% RH non-condensing |
Max Altitude | 2000m |
Safety | IEC 61010-1 |
EMC | IEC61326-1 |
Dimensions | 410 x 250 x 270 mm (16.4 x 9.84 x 10.63 ins) |
Weight | 14.5 kg (excluding test leads) (31.97 lbs) |