Digester Gas Monitor

Digester Gas Monitor

RKI
TF: 002769-HW-RKI-069
Overview

RKI is proud to introduce our Digester Gas Monitor. Gas from waste digesters contains high levels of methane, CO2, and H2S, with little to no oxygen present. The RKI gas monitor checks for all these gases on a cyclic basis. A powerful air aspirator pulls a sample from up to 100 feet away. Since digester gas contains high humidity and high H2S, both of which can cause damage to sampling systems, the RKI Digester Gas Monitor is designed to handle these with no damage to the sampling system or sensors. The sample is filtered through a series of dirt, dust, and moisture stopping filters, and these filters are automatically blown back and cleaned out with fresh air at the end of each cycle.

RKI Controller UsedBeacon 410 with special firmware structured to meet product requirements.
Input Power100/115/220 VAC ± 10% or 24VDC
Enclosure• NEMA 4X enclosure with a window for viewing the gas readings on an LCD display, flow meter, and any other items which require visibility. • For indoor or outdoor use.
Sampling MethodAir Aspirator (compressed air source is required)
Sample Filtering• Internal water trap automatically drained after each detection cycle with a 30 second blowback purge. • Internal gas dryer to dry the sample after it leaves the hydrophobic in line filter.
Flow RateSystem flow rate 3 SCFH.
Flow Meters0 – 5 SCFH Flow meter for total flow. 0 – 0.5 SCFH Flow meter with valve for H2S sample flow. 0 – 2 SCFH Flow meter with valve for H2S dilution flow.

Maximum Inlet/Exhaust

 

Tubing Length

100 ft.
Response TimeT90 in 30 seconds when gas applied directly to sample in fitting during test cycle.

Target Gases/Detection

 

Ranges

• Methane: 0 – 100 % Volume • Oxygen: 0 – 25% Volume • CO2: 0 – 50% Volume • H2S: 0 – 1000 PPM using internal dilution (optional 0 – 3000 and 0 – 5000PPM range)
Sensors• Methane and CO2: NDIR (non-dispersive infrared) sensors • Oxygen and H2S: Long life electrochemical sensor
Operating Temperature/Humidity• 0°C – 40°C (32°F – 104°F) • 0 – 100% Relative Humidity
Alarms• Visual LED alarms (viewed through window) • Audible buzzer alarm (on housing bottom) • Optional loud horn/strobe alarm (on housing top)
Outputs• 4-20 mA for each active sensor • Modbus RTU RS-485
Size24”H x 24”W x 10”D (61cm H x 61cm W x 25.4cm D)
Wire EntryThree 3/4” Conduit Hubs on bottom of enclosure

Measurement time is just 4 minutes, taken at periodic cycles. Cycle time is selectable, with settings for cycle time of 1 hour, 4 hours, 8 hours, 24 hours, or 7 days. A cycle can also be initiated anytime by pressing a button. After each cycle, the sensors and sampling system are flushed with fresh air so as to minimize corrosion caused by the high H2S content. The system is fault tolerant minimizing the possibility of expensive repairs or downtime.

System integrity is maintained at all times using a flow fail monitoring device which provides a fail alarm and relay if there is ever a problem with the flow system, such as a blockage, or if the air aspirator compressed air supply is removed or interrupted.