Direct Connect Gas Sensors

Direct Connect Gas Sensors

RKI
TF: 002763-HW-RKI-063
Overview

The RKI Direct Connect series gas sensors are highly reliable and very cost effective for the detection of common gas hazards. The direct connect series are available for LEL, H2 Specific LEL, LEL IR, Oxygen, H2S, CO, CO2, and for a variety of toxic gases. The sensors for LEL, H2, Oxygen, H2S, CO2, and Carbon Monoxide are explosion-proof with flame arrestors, and approved for use in hazardous areas (Class 1, Div. 1 Groups B, C, D). An optional non-explosion proof version is available for oxygen, H2S, CO, and CO2 for use in Class 1 Div 2.

Sensor Only

65-2494RK

 

*65-2510RK

65-2495RK65-2496RKSee Chart Below61-0198RK-02
61-0198RK-03
61-0198RK-05
61-0198RK-10
Measuring Range0-25% Vol.0-100 ppm0-300 ppm0 – 5000ppm
0 – 5.0%Vol.
0 – 50%Vol.
0 – 100%Vol.
Lower Detectable Limit (LDL)0.1% Vol.2% of full scale
Response Time (T-90)20 seconds or less35 seconds or less60 seconds or less30 seconds or less
Accuracy+/- 5% of full scale (0.5% volume for oxygen)
Life Expectancy2 years withnormal service2 to 3 years with normal service5 years plus with
normal service
Operating Environment
LocationIndoor or outdoor, Class I, Div. 2
Temperature-4°F to 122°F
-20°C to 50°C
14°F to 104°F
-10°C to 40°C
-40°F to 122°F
-40°C to 50°C
Humidity0 – 99% RH non condensing
Housing
Housing J-BoxCast aluminum, explosion-proof
SensorAluminum
ControllersCompatible with the following controllers: Beacon 110, Beacon 200, and Beacon 410A
WarrantyOne year materials and workmanship

The Direct Connect sensors can be used in two different ways. The sensors can be mounted directly to the controllers as a complete stand alone system, or they can be mounted to explosion proof junction boxes for remote detection.

The toxic sensors are electrochemical type plug-in sensors, which provide high specificity, fast response, and long life. The plug-in design allows quick replacement in the field with no tools required. Toxic sensors are designed for use in Class I, Div. 2 hazardous locations. Sensors are available for NH3, AsH3, Cl2, ClO2, HCN, PH3, and SO2.