RKI T3A Gas Detector

RKI T3A Gas Detector

RKI
TF: 002758-HW-RKI-058
Overview

The T3A Series Gas Detector ambient air hazardous gas detector is a versatile assembly  that uses an electrochemical, infrared, catalytic bead sensor element to detect a variety of gases. Wired power (12 to 35 VDC) with 4-20 mA analog and RS-485 Modbus outputs standard. Magnetic switches allow for non-intrusive calibration while in the field as well as full system settings and diagnostics.


 

Sensor TypeElectrochemical, infrared, catalytic bead
Operating VoltageWired power (3-Wire) 12 to 35 VDC
Power Draw2 Watts maximum
Protection

Power electromagnetic interference (EMI) filter

4-20 mA surge suppression

RS-485 surge suppression

Display Screen102×64 Resolution graphical LCD screen transflective (sunlight readable) with white LED backlight
Interface

3 Push-buttons (MENU, ADD and SUB)

3 Magnetic non-intrusive switches for calibration

Customizable Settings2 Individual-configurable alarm LED/relay set-points
Temperature Range-40°C to +54°C (-40°F to +129°F)
Output (digital)RS-485 modbus
Wired (Analog) Output

4-20 mA (3-Wire)

Fault terminal, wet relay contact. Has it’s own power.

Optional 2 dry-contact relays with replaceable 4 amp fuses.

Product Dimensions5.5 in, L x 6 in. W x 7 in. H (8 in. W x 17 in. H Max. dimensions with attachments)
Total Weight6 lbs.

Remote Sensor Kit

 

(Optional Additional Feature)

Remote sensor kit with enclosure (5 pin)

• Electrochemical sensor max. length: 250 feet

• Infrared sensor max. length: 40 feet

• Catalytic bead sensor max. length: 15 feet

Hazardous Location

 

Approvals

Main Enclosure

Certified explosion / flame proof CQPSUS

Class I, Division 1 & 2, Groups B, C & D

Nema 3, 4, 4X, 7 (B, C, D) 9 (E, F, G)

Temp.= -20°C to +60°C

Sensor Housing

Certified explosion / flame proof CQPSUS

Class I, Division 1 & 2, Groups B, C & D

Temp.= -40°C to +60°C

Note: Certification only applies to some gases. Toxic gases not certified for Div. 1 locations are suitable for Div. 2 applications but have no third party approval.

ControllersControllers compatible with all RKI Beacon controllers, as well as most DCS / PLC systems: Beacon 110, Beacon 200, Beacon 410A, Beacon 800, and MC-6400
Warranty1-Year warranty for electronics and sensor
  • Electrochemical, Infrared or catalytic bead sensors
  • Wire powered (3-Wire), 12 to 35 VDC operating voltage
  • Operating temperature range -40°C to +60°C
  • LCD display with LED back-light
  • 3 Push-button interface (ADD, MENU, SUB)
  • Non-intrusive buttons using magnetic wand